1

2

WATER HEATERS: SERIE-W

In an example below water is heated using boiler water. Temperatures of the boiler water are 90 – 40 ºC and of the water 5 – 55 ºC. Water flow amounts in both of the circuits are equal. Pressure losses over the HE in both circuits are a. 25 kPa (0.25bar).

Type Heasting Effect Water Flow Measures Weight
kW m³/h Φ/S kg
240-120-9W 73 1,3 240/56 15
240-120-15W 127 2,2 240/70 17
240-120-23W 200 3,5 240/86 19
240-120-35W 309 5,3 240/112 23
240-120-51W 454 7,8 240/152 27
240-120-81W 727 12,5 240/220 33
240-120-105W 945 16,3 240/276 41
240-120-135W 1218 21,0 240/346 48
240-120-151W 1363 23,4 240/383 53

Φ = diameter (mm)
S = thickness of the package (mm)

In an example below water is heated using boiler water. Temperatures of the boiler water are 85 – 65ºC and of heat up circuit 50 – 70. Water flow amounts in both of the circuits are equal Pressure losses over the HE in both of the circuits are a. 20 kPa (0.20bar).

 

Type Heasting Effect Water Flow Measures Weight
kW m³/h Φ/S kg
240-120-9W 27 1,2 240/56 15
240-120-15W 47 2,0 240/70 17
240-120-23W 75 3,2 240/86 19
240-120-35W 115 4,9 240/112 23
240-120-51W 169 7,3 240/152 27
240-120-81W 270 11,6 240/220 33
240-120-105W 353 15,1 240/276 41
240-120-135W 452 19,4 240/346 48
240-120-151W 506 21,7 240/383 53

Φ = diameter (mm)
S = thickness of the package (mm)

Contact information

Raucell Oy

Räiskylänkatu 10
FI-11120 Riihimäki, Finland

Tel. +358 19 739 554
GSM +358 40 500 2483
E-mail: sales[at]raucell.com
www.raucell.com

Patents

A structure for the end of pressure vessels, most applicably plate heat exchangers, for reducing the effects of movement changes and vibrations caused by variations in internal pressure and temperature. The end is made up of a heat transfer plate and an end part in such a way that the end part is connected by welding to the shell of the outer surface of the heat exchanger stack, forming an enclosed chamber on the end of the heat exchanger, into which chamber higher pressure than the external pressure level is brought and/or generated. The higher pressure receives and dampens, via a heat transfer plate, vibration and pressure shocks harmful to the heat exchanger structure in the medium circuits of the heat exchanger.

FI126717 B (2017)

Technology
EPO 0903554 B1 (2004)
FI 79409 (1989 Original)
Technology Licensing